EM TEST CNI 501x-series 1-Phase Coupling/Decoupling Networks 10kV
Description
CNI 501x-series Combined 1-Phase Coupling/Decoupling Networks for Burst and Surge Testing up to 10 kV
EM TEST CNI 501x-series 1-Phase Coupling/Decoupling Networks are used to couple EFT/Burst pulses and Surge pulses on to AC and/or DC supply lines.
The CNI 501x-series coupling/decoupling networks are fully compliant meeting the standard requirements of IEC/EN 61000-4-4 and IEC/EN 61000-4-5. Residual voltage levels are carefully considered as well as the value of the decoupling inductors to meet the requirements regarding voltage drop at the rated current of each type of CDN.
The CNI 501Bx series also fully complies with the surge test requirements outlined in ANSI/IEEE C62.41.
MODEL OVERVIEW
CNI 501 S1 250V, 100A AC, 75V, 100A DC up to 5.5 kV
CNI 501B S1 250V, 32A AC up to 7 kV
CNI 501B S2 300V, 16A AC, 1,000V, 16A DC up to 7 kV
CNI 501B S3 300V, 32A AC, 1,000V, 32A DC up to 7 kV
CNI 501B S4 300V, 63A AC, 1,000V, 63A DC up to 7 kV
CNI 501B9 250V, 100A AC, 75V, 100A DC up to 7 kV
Features
- Combined coupler for EFT/Burst and Surge testing
- Surge as per ANSI/IEEE C62.41 (models CNI 501Bx only)
- LEDs indicate active mode and coupling
- Automatic selection of Surge impedance
- Fully remote controlled by EM TEST generators
- Meets requirements up to 1,000V DC
Specifications
TECHNICAL DETAILS (5.5KV MODELS) | |
CNI 501 S1, 5.5KV | |
Single phase CDN | according to EN/IEC 61000-4-4 and EN/IEC 61000-4-5 for Burst up to 5.5kV
Surge up to 5kV |
EUT supply | 250V, 100A AC
48V, 100A DC |
Dimensions Size | 19″ / 6 HU |
Weight | approx. 55kg |
TECHNICAL DETAILS (7KV MODELS) | |
CNI 501B S1, 7KV | |
Single phase CDN | according to EN/IEC 61000-4-4, EN/IEC 61000-4-5 and ANSI/IEEE C62.41 for Burst up to 5.5kV
Surge up to 7kV |
EUT supply | 250V, 32A AC |
Dimensions Size | 19″ / 6 HU |
Weight | approx. 20kg |
CNI 501B S2, 7KV | |
Single phase CDN | according to EN/IEC 61000-4-4, EN/IEC 61000-4-5 and ANSI/IEEE C62.41 for Burst up to 5.5kV
Surge up to 7kV |
EUT supply | 300V, 16A AC
1,000V, 16A DC |
Dimensions Size | 19″ / 6 HU |
Weight | approx. 25kg |
CNI 501B S3, 7KV | |
Single phase CDN | according to EN/IEC 61000-4-4, EN/IEC 61000-4-5 and ANSI/IEEE C62.41 for Burst up to 5.5kV
Surge up to 7kV |
EUT supply | 300V, 32A AC
1,000V, 32A DC |
Dimensions Size | 19″ / 6 HU |
Weight | approx. 28kg |
CNI 501B S4, 7KV | |
Single phase CDN | according to EN/IEC 61000-4-4, EN/IEC 61000-4-5 and ANSI/IEEE C62.41 for Burst up to 5.5kV
Surge up to 7kV |
EUT supply | 300V, 63A AC
1,000V, 63A DC |
Dimensions Size | 19″ / 6 HU |
Weight | approx. 32kg |
TECHNICAL DETAILS (10KV MODEL) | |
CNI 501B9, 7KV | |
Single phase CDN | according to EN/IEC 61000-4-4, EN/IEC 61000-4-5 and ANSI/IEEE C62.41 for Burst up to 5.5kV,
Surge up to 7kV |
EUT supply | 250V, 100A AC
75V, 100A DC |
Dimensions Size
(HxWxD) |
19” / 6 HU
286 x 448 x 503 (mm) |
Weight | approx. 25kg |
Mains | Supply: 230VAC +10%/-15%
Frequency: 50/60Hz Fuses: 2 x T 2AT Power: approx. 70W |
GENERAL DATA | |
COUPLING MODES | |
IEC 61000-4-4 | Line(s) to Reference Ground; all combinations |
IEC 61000-4-5 | Line to Line with a 2ohm source impedance
Line(s) to PE with a 12ohm source impedance |
ANSI/IEEE C62.4 | (supporting models only)
Surge coupling with a 2ohm source impedance for all lines |