Bacharach Fyrite INSIGHT Residential Combustion Analyzer
Description
Combining revolutionary new technology developed by Bacharach engineers, such as software field upgradeability and the B-Smart® Sensors Calibration Program; the Fyrite® INSIGHT® allows technicians and HVAC/R service representatives the ability to upgrade and calibrate their equipment without having to send it to the manufacturer, minimizing downtime.
This five-in-one steady state combustion analyzer includes: a room air CO test instrument, a flue gas CO tester, dual channel digital thermometer (up to 999ºF), and a digital manometer (which measures draft, gas pressure, ESP, and up to +/- 100 INWC).
Capable of providing up to 100 combustion, pressure, and temperature records, the INSIGHT® also can display measurement results for up to eight different fuels on its backlit, custom readout graphic LCD display. In addition, specific information can also be uploaded to a PC or printed via an infrared printer.
Bacharach's unique smart sensor exchange program delivers new B-Smart® Sensors right to the user. Just a simple “pop out and pop in” replacement of the sensor permits self calibration with no gas or guess work required. Providing the quickest and easiest calibration options to date, the B-Smart® Sensors assure accurate performance with no downtime.
Features
- Five Tools in ONE!
- Combustion and efficiency analyzer – (8) different fuels
- Room air CO test instrument
- Flue gas CO tester (CO air free)
- Dual channel digital thermometer (Up to 999°F)
- Digital manometer (draft, gas pressure, ESP, up to 28 WC”)
- New B-Smart® Technology
- Self calibration
- Easy access to sensors
- User Diagnostics
- O2 and sensor life
- Calibration reminders
- Graphic LCD Display
- Backlight, customizable readout and zoom feature
- PC Based Software and Reporting package (optional)
- Customize w/ company logo
- Upload custom fuels
- Software updates
- Test data storage
Specifications
Measurement Ranges |
Combustion Air/ Ambient Temperature |
-4 to 600°F (-20 to 316°C) |
Flue Gas Temperature |
-4 to 1200°F (-20 to 649°C) |
|
Oxygen |
0.0 to 20.9% O2 |
|
Carbon Monoxide |
0 to 2,000 PPM CO |
|
Draft/Differential Pressure |
-100 to +100 in. WC |
|
Combustion Air/ Ambient Temperature |
-4 to 600°F (-20 to 316°C) |
|
Calculated Ranges |
Combustion Efficiency |
0.1 to 100% |
Carbon Dioxide |
0.1 to a fuel dependant max. value in percent |
|
Carbon Monoxide (air free) |
0 to 9,999 PPM |
|
Excess Air |
0 to 250% x 0 to 250% |
|
Combustion Efficiency |
0.1 to 100% |
|
Selectable Fuels |
Natural Gas |
|
Oil #2, Oil #4, Oil #6 |
||
Propane, Coal, Wood |
||
Kerosene |
||
Power |
Four disposable ‘AA’ alkaline batteries (included) |
|
Battery Life |
Minimum of 20 hours |
|
Size |
8.0″H x 3.6″W x 2.3″D |
|
Weight |
16 oz. with batteries |
|
Warranty |
2 years, including sensors (1 year for O2 sensors) |
|
Instructional DVD |
Included |