Bacharach HGM-MZ Halogen Multi-Zone Gas Leak Monitor
Description
Bacharach’s Multi-Zone Gas Leak Monitors offer superior performance, flexibility and functionality for low level continuous monitoring of refrigerant gases used in most commercial systems including: Chlorofluorocarbons (CFC), Hydro chlorofluorocarbons (HCFC), Hydro fluorocarbons (HFC), Ammonia (NH3) and Carbon Dioxide (CO2).
These state-of-the-art fixed gas monitors lead the industry in performance, integration capabilities, initial cost and cost of ownership. Capable of detecting more than 38 refrigerant gases, the Multi-Zone system is compliant with ASHRAE standard 15-2007, is ETL Energy Saving Listed, meets California Code Regulations for Refrigerant Monitors and is EN 14624 and CE certified.
Features
- Proprietary infrared sensing technology virtually eliminates false alarms and extends sensor life
- No calibration required
- Low detection limits enable leaks to be found early, reducing energy and refrigerant consumption
- Fastest sampling rate with the longest sampling distance in the industry at 1,200 feet
- Large Graphic LCD for easy set-up and real-time monitoring
Specifications
Product Type |
The Multi-Zone Gas Leak Monitor is a multiple area monitoring system for low level continuous monitoring of refrigerant gases used in most commercial systems including; CFC, HCFC, HFC and Ammonia. System design supports compliance to gas monitoring requirements of ANSI/BSR ASHRAE 15-1994. |
||
Gas Library |
HGM-MZ: |
CFC: R11, R12, R113, R114, R502, HFP |
|
AGM-MZ: |
Ammonia (NH3), R717 |
||
CO2-MZ: |
Carbon Dioxide (CO2), R744 |
||
Sensitivity |
All gases 1 ppm (R11 ± 10 ppm ± 15% of reading 0-1000 ppm) |
||
Measuring Range |
HGM-MZ: |
All gases 0 to 10,000 ppm |
|
AGM-MZ: |
Ammonia 25 to 10,000 ppm |
||
CO2-MZ: |
Carbon Dioxide 0 to 8,000 ppm |
||
Accuracy |
HGM-MZ: |
±1 ppm ±10% of reading from 0-1,000 ppm (R11, R22, R13: ±10 ppm |
|
AGM-MZ: |
±10 ppm ±10% of reading from 0-1,000 ppm |
||
CO2-MZ: |
±5 ppm ±5% of reading from 0-1,000 ppm, ±10% of reading from 1,000 |
||
Front Panel |
3 indicator lights Green = Monitor is powered on. LED glows during normal operation; flashes when unit is in warm-up mode Red = Alarm. LED flashes when any point has exceeded the alarm setting Yellow = Fault. LED flashes when there is a system fault
|
||
Size & Weight |
12.23″ H x 13.7″ W x 4.96″ D / 15lbs. |
||
Temperature Drift |
HGM-MZ: |
±0.8% (R134A) of reading per Degrees C between purge cycles |
|
AGM-MZ: |
1.5 ppm per Degrees C between purge cycles |
||
CO2-MZ: |
Less than 1 ppm per Degrees C between purge cycles |
||
Coverage |
4 point standard, expandable to 16 points in 4 point increments |
||
Detector Type |
Infrared Non-Dispersive |
||
Sampling Mode |
Automatic or Manual (hold) |
||
Re-Zero |
Auto or on Zone Change |
||
Response Time |
5 to 120 seconds — depending on air line length and number of zones |
||
System Noise |
Less than 40dB(A) @ 10 feet (3m) |
||
Monitoring Distance |
1,200 ft. maximum for combined length of sample + exhaust tubing (each zone) |
||
Conditional System |
Dual optional 4-20mAdc isolated outputs. Channel 1 = zone area, Channel 2 = PPM |
||
Alarms |
Four SPDT alarm contacts are provided (rated 5 Amps at 250 volts). Three assigned to PPM level alarms, one assigned to system faults |
||
Communications |
Full two-way communications with proper remote display module or building management system via RS485 MODBUS-RTU serial interface. RS-232C communications port standard |
||
Power Safety Mode |
Fully automatic system reset. All programmed parameters retained |
||
Operating Temp. |
32 to 122 °F (0 to 50 °C) |
||
Ambient Humidity |
5% to 90% RH (non-condensing) |
||
AC Power |
100 to 240 VAC, 50/60 Hz, 20 W |
||
Certification |
UL 61010-1, Can/CSA 22.2 No. 61010-1 & CE Mark |
||
Warranty |
2 years from date of shipment |
||
Altitude Limit |
6,562 ft (2,00 m) |