Sorensen XFR 300-4 Low Profile DC Power Supply 300V 4A 1200W
Description
Sorensen XFR 300-4 Low Profile DC Power Supply 300V 4A 1200W is the smart choice for research, product development and production test applications such as R&D, magnet control, product design, ATE, process control, electroplating and burn-in. The unique features of XFR make it the best choice for applications where high power and a wide adjustment of output voltage or current are required in a full 19-inch rack package. Choose from twenty 2800-watt and 1200-watt models.
Zero voltage, or “soft” switching, provides significant benefits. Switching transients are virtually eliminated and noise performance is closer to linear levels. Efficiency is increased, heat generation is decreased, and stress on the switching transistors is reduced – improving reliability (MTBF).
Unlike most competitive products, XFR generates full power at full rated current over its total operating range of 0 to 50° C without derating. XFR is also designed with excellent thermal management, so units can be stacked in rack mounts without leaving ventilation space between each unit.
The low thermal generation and high efficiency of “soft” switching technology allows for the packaging of 1200 watts in a 1.75-inch (1 U) high, 19-inch rack mount chassis, providing 20% more power than any competitive product in the same size package.
Features
- Analog programming
- Zero voltage “soft switching”
- Constant voltage or constant current operation with automatic crossover and mode indication
- Standby/Remote/Local modes
- Front panel button preview of voltage, current, OVP
- Remote sense, 5 V line loss compensation
- LabVIEW® and LabWindows® drivers
Specifications
Common | ||||||
Switching Frequency | XFR 2.8 kW: Nominal 31 kHz (62 kHz output ripple) XFR 1.2 kW: 12 V to 40 V models: nominal 78 kHz (156 kHz output ripple); 60 V to 600 V models: nominal 62.5 kHz (125 kHz output ripple). | |||||
Time Delay | 7 sec maximum from power on until output stable | |||||
Voltage Mode Transient Response Time | < 3 ms for output voltage to recover within 0.5% of its rated voltage after a step change in load current of up to 10% to 90% of rated output | |||||
Maximum Voltage Differential | ±600 Vdc from output to safety ground | |||||
Remote Start/Stop and Interlock | 2.5-15 V signal or TTL-compatible input, selectable logic | |||||
Remote Analog Programming | Voltage and current programming inputs (source must be isolated): 0-5 k, 0-10 k resistances; 0-5 V, 0-10 V (default) voltage sources | |||||
Remote Analog Monitoring | Voltage and current monitor outputs 0-5 V, 0-10 V (default) ranges for 0-100% of output | |||||
Remote Programming & Monitoring Accuracy | 1% zero to full scale output for the default range | |||||
Maximum Remote Sense Line Drop Compensation | 5 V / line (Line drop is subtracted from total voltage available at supply output.) | |||||
Front Panel Voltage and Current Control | 10-turn voltage and current potentiometers | |||||
Front Panel Voltage Control Resolution | 0.02% of maximum voltage | |||||
Main Output Connector | XFR 2.8 kW: 7.5 – 100 V models: nickel-plated copper bus bars with bus bar cover and strain relief; 150V to 600 V models: 4-terminal, wire clamp connector with cover and strain relief; XFR 1.2 kW: 12 – 40 V models: nickel-plated copper bus bars with bus bar shield; 60 – 600 V models: 4-terminal wire clamp connector with strain relief | |||||
Approvals | NRTL approved and CE-marked to UL Std. No. 61010-1, CAN/CSA-C22.2 No. 61010-1-04, EN 610101-1 (Equipment Class I, Pollution Degree 2, Installation Category II) Meets USA EMC standard: FCC, part 15B, Class A; Meets Canadian EMC standard: ICES-001, Class A. | |||||
Input | ||||||
Input Voltage Ranges | XFR 2.8 kW: 190-264 Vac, 1φ (24.3 A @ 208 Vac; 20.5 A @ 230 Vac typical), 47-63 Hz; Option: M2 3φ 208 Vac input XFR 1.2 kW: 85-130 Vac or 190-264 Vac, 1φ (17 A @ 120 Vac; 8.8 A @ 230 Vac typical), 47-63 Hz. Automatic range detect. | |||||
AC Input Connector | Type 3-terminal, 34 A, 250 V, wire clamp connector with strain relief cover | |||||
Protection Features | ||||||
Over-voltage protection | ||||||
Over-temperature protection | ||||||
Environmental | ||||||
Operating Temperature | XFR 2.8 kW: 0 to 50°C, XFR 1.2 kW: 0 to 50°C | |||||
Storage Temperature | -20°C to 70°C | |||||
Humidity (Non-condensing) | Up to 90% RH, non-condensing | |||||
Physical | ||||||
Model |
XFR 2.8 kW |
XFR 1.2 kW |
||||
Dimensions |
Width: 19” (429.4 mm) |
Width: 19” (429.4 mm) |
||||
Weight |
33 lb (15 kg) |
18 lb (8.2 kg) |
||||
Output Ratings | ||||||
Model |
Output Voltage |
Output Current |
Output Power |
|||
XFR 7.5-300 |
0-7.5 V |
0-300 A |
2250 W |
|||
XFR 12-220 |
0-12 V |
0-220 A |
2640 W |
|||
XFR 20-130 |
0-20 V |
0-130 A |
2600 W |
|||
XFR 33-85 |
0-33 V |
0-85 A |
2805 W |
|||
XFR 40-70 |
0-40 V |
0-70 A |
2800 W |
|||
XFR 60-46 |
0-60 V |
0-46 A |
2760 W |
|||
XFR 100-28 |
0-100 V |
0-28 A |
2800 W |
|||
XFR 150-18 |
0-150 V |
0-18 A |
2700 W |
|||
XFR 300-9 |
0-300 V |
0-9 A |
2700 W |
|||
XFR 600-4 |
0-600 V |
0-4 A |
2400 W |
|||
XFR 7.5-140 |
0-7.5 V |
0-140 A |
1050 W |
|||
XFR 12-100 |
0-12 V |
0-100 A |
1200 W |
|||
XFR 20-60 |
0-20 V |
0-60 A |
1200 W |
|||
XFR 35-35 |
0-35 V |
0-35 A |
1225 W |
|||
XFR 40-30 |
0-40 V |
0-30 A |
1200 W |
|||
XFR 60-20 |
0-60 V |
0-20 A |
1200 W |
|||
XFR 100-12 |
0-100 V |
0-12 A |
1200 W |
|||
XFR 150-8 |
0-150 V |
0-8 A |
1200 W |
|||
XFR 300-4 |
0-300 V |
0-4 A |
1200 W |
|||
XFR 600-2 |
0-600 V |
0-2 A |
1200 W |
|||
Line Regulation | ||||||
Model |
Voltage |
Current |
||||
XFR 7.5-300 |
2.75 mV |
32 mA |
||||
XFR 12-220 |
3.2 mV |
24 mA |
||||
XFR 20-130 |
4 mV |
15 mA |
||||
XFR 33-85 |
5.3 mV |
10.5 mA |
||||
XFR 40-70 |
6 mV |
9 mA |
||||
XFR 60-46 |
8 mV |
6.6 mA |
||||
XFR 100-28 |
12 mV |
4.8 mA |
||||
XFR 150-18 |
17 mV |
3.8 mA |
||||
XFR 300-9 |
32 mV |
2.9 mA |
||||
XFR 600-4 |
62 mV |
2.4 mA |
||||
XFR 7.5-140 |
2.75 mV |
16 mA |
||||
XFR 12-100 |
3.2 mV |
12 mA |
||||
XFR 20-60 |
4 mV |
8 mA |
||||
XFR 35-35 |
5.5 mV |
5.5 mA |
||||
XFR 40-30 |
6 mV |
5 mA |
||||
XFR 60-20 |
8 mV |
4 mA |
||||
XFR 100-12 |
12 mV |
3.2 mA |
||||
XFR 150-8 |
17 mV |
2.8 mA |
||||
XFR 300-4 |
32 mV |
2.4 mA |
||||
XFR 600-2 |
62 mV |
2.2 mA |
||||
Load Regulation | ||||||
Model |
Voltage |
Current |
||||
XFR 7.5-300 |
6.5 mV |
65 mA |
||||
XFR 12-220 |
7.4 mV |
49 mA |
||||
XFR 20-130 |
9 mV |
31 mA |
||||
XFR 33-85 |
11.6 mV |
22 mA |
||||
XFR 40-70 |
13 mV |
19 mA |
||||
XFR 60-46 |
17 mV |
14.2 mA |
||||
XFR 100-28 |
27 mV |
10.6 mA |
||||
XFR 150-18 |
35 mV |
8.6 mA |
||||
XFR 300-9 |
65 mV |
6.8 mA |
||||
XFR 600-4 |
125 mV |
5.8 mA |
||||
XFR 7.5-140 |
6.5 mV |
33 mA |
||||
XFR 12-100 |
7.4 mV |
25 mA |
||||
XFR 20-60 |
9 mV |
17 mA |
||||
XFR 35-35 |
12 mV |
12 mA |
||||
XFR 40-30 |
13 mV |
11 mA |
||||
XFR 60-20 |
17 mV |
9 mA |
||||
XFR 100-12 |
27 mV |
7.4 mA |
||||
XFR 150-8 |
35 mV |
6.6 mA |
||||
XFR 300-4 |
65 mV |
5.8 mA |
||||
XFR 600-2 |
125 mV |
5.4 mA |
||||
Meter Accuracy | ||||||
Model |
Voltage (1% of Vmax + 1 count) |
Current (1% of lmax + 1 count) |
||||
XFR 7.5-300 |
0.09 V |
4 A |
||||
XFR 12-220 |
0.13 V |
2.3 A |
||||
XFR 20-130 |
0.3 V |
1.4 A |
||||
XFR 33-85 |
0.43 V |
0.95 A |
||||
XFR 40-70 |
0.5 V |
0.8 A |
||||
XFR 60-46 |
0.7 V |
0.56 A |
||||
XFR 100-28 |
1.1 V |
0.38 A |
||||
XFR 150-18 |
1.6 V |
0.19 A |
||||
XFR 300-9 |
4 V |
0.1 A |
||||
XFR 600-4 |
7 V |
0.05 A |
||||
XFR 7.5-140 |
0.09 V |
1.5 A |
||||
XFR 12-100 |
0.13 V |
1.1 A |
||||
XFR 20-60 |
0.3 V |
0.7 A |
||||
XFR 35-35 |
0.4 V |
0.45 A |
||||
XFR 40-30 |
0.5 V |
.04 A |
||||
XFR 60-20 |
0.7 V |
0.3 A |
||||
XFR 100-12 |
1.1 V |
0.13 A |
||||
XFR 150-8 |
1.6 V |
0.09 A |
||||
XFR 300-4 |
4 V |
0.05 A |
||||
XFR 600-2 |
7 V |
0.03 A |
||||
Output Ratings | ||||||
Model |
Output Noise (0-20 MHz) |
Output Ripple (rms) |
||||
Voltage (p-p) |
Voltage |
Current |
||||
XFR 7.5-300 |
100 mV |
10 mV |
1600 mA |
|||
XFR 12-220 |
100 mV |
10 mV |
1200 mA |
|||
XFR 20-130 |
100 mV |
10 mV |
400 mA |
|||
XFR 33-85 |
100 mV |
15 mV |
300 mA |
|||
XFR 40-70 |
150 mV |
15 mV |
200 mA |
|||
XFR 60-46 |
150 mV |
15 mV |
100 mA |
|||
XFR 100-28 |
175 mV |
25 mV |
80 mA |
|||
XFR 150-18 |
200 mV |
25 mV |
40 mA |
|||
XFR 300-9 |
400 mV |
40 mV |
20 mA |
|||
XFR 600-4 |
500 mV |
100 mV |
10 mA |
|||
XFR 7.5-140 |
75 mV |
9 mV |
500 mA |
|||
XFR 12-100 |
75 mV |
9 mV |
500 mA |
|||
XFR 20-60 |
75 mV |
9 mV |
500 mA |
|||
XFR 35-35 |
120 mV |
9 mV |
300 mA |
|||
XFR 40-30 |
150 mV |
9 mV |
200 mA |
|||
XFR 60-20 |
150 mV |
9 mV |
100 mA |
|||
XFR 100-12 |
150 mV |
9 mV |
100 mA |
|||
XFR 150-8 |
150 mV |
18 mV |
50 mA |
|||
XFR 300-4 |
200 mV |
27 mV |
25 mA |
|||
XFR 600-2 |
400 mV |
72 mV |
15 mA |