California Instruments 10001iX AC Power Source 10kVA
Description
The iX Series II represents a new generation of AC and DC power source that addresses increasing demands on test equipment to perform more functions at a lower cost. By combining a flexible AC/DC power source with a high performance power analyzer, the iX Series II systems are capable of handling complex applications that have traditionally required multiple instruments.
The sleek integrated approach of the iX Series II avoids the cable clutter that is commonly found in AC test systems. The i/iX Series II is rack mountable with a 4U chassis design. All connections are made internally and the need for external digital multimeters, power harmonics analyzer and current shunts or clamps is completely eliminated. Using a state of the art digital signal processor in conjunction with precision high resolution A/D converters, the iX Series II provides more accuracy and resolution than can be found in some dedicated harmonic power analyzers. Since many components in the iX Series II are shared between the AC/DC source and the power analyzer, the total cost of the integrated system is less than the typical cost of a multiple unit system.
For less demanding applications, the Compact iX Series provides similar output and transient capabilities as the iX Series II, as well as basic measurements.
Features
- 3000 VA to 15000 VA of AC Output Power
- Combines AC/DC source and power analyzer
- Harmonic analysis of Voltage and Current
- Programmable Impedance
- AC, DC and AC+DC Output Modes
- Multiple Chassis Configurations
- Powerful output transient generation
- High Crest Factor Capability
- Arbitrary waveform generation
- IEC 61000-3-2 and IEC 61000-3-3
Specifications
Operating Modes |
||||||||
Model |
iX Series II |
i Series II |
||||||
Modes |
AC, DC or AC+DC |
AC or DC |
||||||
AC Output Mode |
||||||||
Frequency |
Range: 16.00-1000 Hz (Note: Voltage on 300 V range derates from 300 Vrms max at 500 Hz to 150 Vrms max at 1000 Hz; See V-F rating chart. below) |
|||||||
Total Power |
3001i/iX: 3000 VA, 5001i/iX: 5000 VA, 9003i/iX: 3000 VA 3ø, with mode iX: 9000 VA 1ø, 10001i/iX: 10000 VA, 15001i/iX: 15000 |
|||||||
Load Power Factor |
0 to unity at full output VA |
|||||||
AC Voltage Mode |
||||||||
Voltage Ranges
Output Noise |
Range |
VLow |
VHigh |
|||||
AC |
0-150 V |
0-300 V |
||||||
AC+DC |
0-150 V |
0-300 V |
||||||
Load Regulation |
< 0.2% |
|||||||
Load Regulation |
< 0.5% DC to 100 Hz, |
|||||||
Line Regulation |
< 0.1% for 10% line change |
|||||||
< 250 mVrms typ., < 500 mVrms max. |
||||||||
Harmonic Distortion (Linear) |
< 1% from 16 – 66 Hz, < 2% at 400 Hz, < 3% at 800 Hz (Full resistive load) |
|||||||
DC Offset |
< 20 mV External Amplitude Modulation: Depth: 0 – 10 %, Frequency: DC – 2 KHz |
|||||||
Isolation Voltage |
300 Vrms output to chassis |
|||||||
AC Mode Current |
||||||||
Model |
Model |
3001 i/iX |
5001 i/iX |
9003 i/iX 3ø |
||||
Steady State AC Current |
300 V range |
11.1 |
18.5 |
11.1 /ø |
||||
|
150 V range |
22.2 |
37.0 |
22.2 /ø |
||||
Note: Constant power mode provides increased current at reduced voltage (See chart below) |
||||||||
Model |
Model |
10001 i/iX |
15001 i/iX |
15003 i/iX 3ø |
||||
Steady State AC Current |
300 V range |
37.0 |
55.5 |
18.5 /ø |
||||
|
150 V range |
74.0 |
111.0 |
37.0 /ø |
||||
Note: Constant power mode provides increased current at reduced voltage (See chart below) |
||||||||
Model |
Model |
3001 i/iX |
5001 i/iX |
9003 i/iX 3ø |
||||
Peak Repetitive AC Current |
High range |
96.0 |
96.0 |
96.0 /ø |
||||
|
Low range |
110.0 |
110.0 |
110.0 /ø |
||||
Model |
Model |
10001 i/iX |
15001 i/iX |
15003 i/iX 3ø |
||||
Peak Repetitive AC Current |
High range |
192.0 |
288.0 |
96.0 /ø |
||||
|
Low range |
220.0 |
330.0 |
110.0 /ø |
||||
Programming Accuracy |
Voltage (rms): ± 0.2 of range, 16 to 1000 Hz, Frequency: ± 0.01 % of programmed value, Current Limit: ± 0.5 % of programmed value, Phase: < 1.5° with balanced load at 50/60 Hz |
|||||||
Programming Resolution |
Voltage (rms): 100 mV, Frequency: 0.01 Hz from 16 – 81.91 Hz, 0.1 Hz from 82.0 – 819.1 Hz, 1 Hz from 820-1000 Hz, Current Limit: 0.1 A, Phase, 0.1° |
|||||||
Output Relay |
Push-button controlled or bus controlled output relay |
|||||||
Output Impedance (iX Only) |
Programmable Z on 3001iX, 5001iX, 9003iX and 15003iX (3ø mode only) for 50 Hz fundamental |
|||||||
Resistive |
Range: 17 – 1000 mOhm,resolution: 4 mOhm accuracy, 2 % FS |
|||||||
Inductive |
Range: 230 – 1000 μH, resolution: 4 μH, accuracy: 2 % FS |
|||||||
Measurements – Standard (AC Measurements) |
||||||||
Parameter |
Frequency |
RMS Voltage |
RMS Current |
Peak Current |
||||
Range |
16-500 Hz |
0-300 V |
0-40 A |
0-120 A |
||||
Accuracy* (±) |
< 100 Hz 100 – 500 Hz |
0.5 V + 0.02% 0.1 V + 0.02% |
0.5 A + 0.02% 0.1 A + 0.02% |
0.5 A + 0.02% 0.1 A + 0.02% |
||||
Resolution* |
0.01 Hz |
10 mV |
1 mA |
1 mA |
||||
Parameter |
Crest Factor |
Real Power |
Apparent Pwr |
Pwr Factor |
||||
Range |
0.00-6.00 |
0-6 kW |
0-6 kVA |
0.00-1.00 |
||||
Accuracy* (±) |
0.05 0.05 |
10 W + 0.1% 20 W + 0.1% |
10 VA + 0.1% 20 VA + 0.1% |
0.01 0.02 |
||||
Resolution* |
0.01 |
1 W |
1 VA |
0.01 |
||||
Parameter |
DC Voltage |
DC Current |
Power |
|
||||
Voltage Ranges |
0-300 V |
0-40 A |
0-6 kW |
|
||||
Accuracy* (±) |
150 mV 150 mV |
70 mA 70 mA |
15 W 15 W |
|
||||
Resolution* |
10 mV |
1 mA |
1 W |
|
||||
* Measurement system bandwidth = DC to 48 kHz. Accuracy specifications are valid above 100 counts. Current and Power Accuracy specifications are times two for 10001i/iX /30003i/iX and times three for 15001i/iX and 9003i/iX and 15003i/iX with MODE-iX option when in single phase mode. For 10001i/iX, 15001i/iX and 30003i/ iX, resolution decreases by factor of 10, ranges for current and power increases by factor of three. PF accuracy applies for PF > 0.5 and VA > 50% of range. |
||||||||
Measurements – Harmonics |
||||||||
Parameter |
Frequency Fundamental Harmonics |
Phase |
Voltage |
Current |
||||
Range |
16.00-500.0 Hz / 32.00 Hz – 48.00 kHz |
0.0 – 360.0° |
Fundamental Harmonics 2 – 50 |
Fundamental Harmonics 2 – 50 |
||||
Accuracy* (±) |
0.01% + 0.01 Hz |
2° typ. |
250 mV 0.1% + 250 mV+0.1% /1 kHz |
50 mA/0.1% + 50 mA +0.1% /1 kHz |
||||
Resolution |
0.01 Hz |
0.5° |
10 mV / 10 mV |
10 mA / 10 mA |
||||
* Accuracy specifications are valid above 100 counts. Accuracy specifications are times three for three phase mode. Harmonics frequency range in three phase mode is 32 Hz – 16 kHz. Resolution decreases by factor of 10 for 9003iX and 15003iX with Mode-iX option in 1 phase mode and for 10001iX, 15001iX and 30003i/iX. |
||||||||
DC Mode Output |
||||||||
Power (Max at full scale of DC Voltage Range) |
3001i/iX: 2100 W, 5001i/iX: 3500 W, 9003i/iX: 2100 W/ø 3ø, 6300 W/ø 1ø, 10001i/iX: 7000 W, 15001i/iX: 10500 W, 15003i/iX: 3500 W/ø 3ø, 10500 W/ø 1ø |
|||||||
Voltage Ranges |
Range: Low: 200 Vdc, High: 400 Vdc |
|||||||
Line Regulation |
< 0.1% FS or 10% line change |
|||||||
Output Noise |
< 250 mV rms typ., < 500 mV rms max., (20 kHz to 1 MHz) |
|||||||
Max DC Current (Maximum current at 65% of V Range) |
||||||||
Model |
3001 i/iX |
5001 i/iX |
9003 i/iX |
9003 i/iX 3ø |
||||
400V range |
7.8 |
13 |
23.4 |
7.8 |
||||
200V range |
15.6 |
26 |
46.8 |
15.6 |
||||
Model |
10001 i/iX |
15001 i/iX |
15003 i/iX 3ø |
|||||
400V range |
26 |
39 |
13 |
|||||
200V range |
52 |
78 |
26 |
|||||
Current Limit |
Programmable from 0 A to maximum current for selected range |
|||||||
AC+DC Mode Output |
||||||||
Output Power (iX only) |
Full AC Power if DC component is less than 20% of full scale voltage, Full DC power if DC component is above 20% |
|||||||
Storage |
||||||||
Non Volatile Mem. storage |
16 instrument setups, 200 user defined waveforms |
|||||||
Waveforms |
||||||||
Waveform Types |
i Series II: Sine, iX Series II: Sine, Square, Clipped sine, User defined |
|||||||
User defined waveform storage |
Four groups of 50 user defined arbitrary waveforms of 1024 points for a total of 200 (One group can be active at a time) |
|||||||
System Interface |
||||||||
Inputs |
Remote shutdown, External Sync, Clock/Lock (option) |
|||||||
Outputs |
Function Strobe, Clock/Lock (option) |
|||||||
Protection |
||||||||
Over Load |
Constant Current or Constant Voltage mode |
|||||||
Over Temperature |
Automatic shutdown |
|||||||
Remote Control |
||||||||
IEEE-488 Interface |
IEEE-488 (GPIB) talker listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2 SCPI Syntax |
|||||||
RS232C Interface |
9 pin D-shell connector, Handshake: CTS, RTS, Data bits: 7,8, Stop bits: 1, 2, Baud rate: 9600, 19200, 38400, 57600, 115200, IEEE-488.2 SCPI Syntax (Supplied with RS232C cable) |
|||||||
DC Mode Output |
||||||||
Voltage |
3001 and 9003: 208-240 ± 10% Vac, (L-N, 1ø), All other models: Standard: 208-240 ± 10% Vac, (L-L, 3ø), Option -400: 400-480 ± 10% Vac, (L-L, 3ø) (Input range must be specified when ordering) |
|||||||
Max DC Current (Maximum current at 65% of V Range) |
||||||||
Model |
3001i/iX |
5001i/iX |
9003i/iX |
|||||
187-264V |
25 A |
23 A |
75 A |
|||||
360-528V |
N/A |
12 A |
N/A |
|||||
Model |
10001 i/iX |
15001 i/iX |
15003 i/iX 3ø |
|||||
187-264V |
46 A |
69 A |
69 A |
|||||
360-528V |
24 A |
36 A |
36 A |
|||||
Inrush Current per chassis |
< 100 Apk for 100 μs at 208-240 V, < 50 Apk for 100 μs at 400-480 V |
|||||||
Line Frequency |
50-60 Hz ± 10 % |
|||||||
Efficiency |
75% typical |
|||||||
Power Factor |
0.6 typical |
|||||||
AC Service |
||||||||
Regulatory |
IEC61010, EN50081-2, EN50082-2, CE EMC and Safety Mark requirements |
|||||||
RFI Suppression |
CISPR 11, Group1 , Class A |
|||||||
Rear Panel Connectors |
AC Input & Output terminal block with cover, IEEE-488 (GPIB) connector (rear panel), 9 pin D-Shell RS232C connector*, Remote voltage sense terminal block, System Interface Connector, *RS232 DB9 to DB9 cable supplied |
|||||||
Physical Dimensions |
||||||||
Dimensions |
Height: 7” (178 mm), Width: 19” (483 mm), Depth: 24” (610 mm) |
|||||||
Weight |
per 5001i/iX Chassis: Net: 61 lbs / 28 Kg, Shipping: 115 lbs / 52 Kg |
|||||||
Vibration and Shock |
Designed to meet NSTA project 1A transportation levels |
|||||||
Air Intake/Exhaust |
Forced air cooling, side air intake, rear exhaust. |
|||||||
Operating Humidity |
0 to 95 % RAH, non condensing. |
|||||||
Temperature |
Operating: 0 to 40° C, Storage: -20 to +85° C |