Tenney Classic Series Cycling Test Chamber -40°C to 200°C

Description

Classic Tenney Series – Wide Range Testing The Tenney Classic Series of temperature and humidity test chambers deploys environmentally friendly technology that uses CFC-free refrigerants. The time proven mechanical refrigeration systems are available in single or cascade systems and allow for years of worry-free use. The Classic Series temperature and humidity test chambers are available in 10, 20, 30, 40, and 64 cubic feet models, all of which are available with single or cascading refrigeration systems.

 

Features

  • Semi hermetic refrigeration system
  • Vertical recirculation conditioning system
  • Automatic defrost for door gaskets
  • Non-corroding parts on all humidity capable units
  • Low water protection
  • Open-air low mass nichrome wire heater elements supported by ceramic insulators
  • Single stage or cascade refrigeration system
  • Vapor-Flo I humidity generator (for capable units) with bell jar configuration

Performance

  • Control accuracy: ±0.3°C and  ±2% RH
  • Standard humidity conditions: 20% to 98% RH in the dry bulb range from + 20° to + 85°C, as limited by a 3° dewpoint.
  • Chamber models with a 'S' suffix indicate a single stage refrigeration system with one compressor.
  • Temperature control range: -40°C to +200°C,  ±0.3°C
  • Models TH27 and TH65 are single stage refrigeration systems with a smaller temperature control range: -20°C to +100°C, ±0.2/ ±0.3°C, respectively.
  • Chamber models with the 'C' suffix indicate a cascade refrigeration system and two compressors.
  • Temperature control range: -73°C to +200°C, ±0.3°C

Controller – Watlow F4

  • Single Channel
  • Profiling: Forty Profiles, 256 Steps
  • Automatic & Manual Control
  • 1 Input: Universal Type (RTD is Std.)
  • 4 Digital Inputs
  • 2 Auxiliary Analog Inputs – Optional
  • 2 Control Outputs: Time Proportioned, On/Off, or 4-20 ma
  • 2 Alarm Outputs
  • 8 Digital Event Outputs
  • 2 Retransmit Outputs – Optional
  • Communications: EIA-232 and EIA-485 with Modbus RTU protocol
Print
Email

Specifications

Model 

Non-
humidified

T40S-2

T40C-4

T40C-6

T64S-7.5

T64C-6

T64C-15

Humidified

T40RS-2

T40RC-4

T40RC-6

T64RS-7.5

T64RC-6

T64RC-15

Workspace

W

40(1016)

48(1219)

D

44(1118)

48(1219)

H

40(1016)

48(1219)

Exterior

W

66(1676)

72(1829)

D

73.5(1867)

81.5(2070)

H

80.25(2038)

91(2311)

 Temperature

Non-
humidified

T40S-2

T40C-4

T40C-6

T64S-7.5

T64C-6

T64C-15

Humidified

T40RS-2

T40RC-4

T40RC-6

T64RS-7.5

T64RC-6

T64RC-15

Low

C

-40°C

-73°C

-73°C

-40°C

-73°C

-73°C

High

C

+200°C

+200°C

+200°C

+200°C

+200°C

+200°C

Humidity Capability

20% to 98% RH in the dry bulb range of +20°C or +85°C as limited by a 3°C dew point.

  Test data based on 24°C ambient, sea level, 60 Hz. On 50 Hz or higher than 24°C, ambient performance may be reduced. Consult factory regarding any special cooling requirements. 

40 and 64 cubic foot models

Change Rates in Minutes

Time starting at Ambient to listed temperature. Based on empty chamber.

200°C

35

45

150°C

25

30

93°C

10

15

65°C

5

10

5

5

-18°C

20

10

10

-40°C

120

25

30

-54°C

45

40

45

20

-65°C

60

50

65

35

 Live Load Capacity in Watts (Humidity System Off)

Temperature

+10°C

           

-18°C

1000

4500

-40°C

100

1000

-54°C

1200

2000

1200

4000

-65°C

900

1500

800

2500

40 and 64 cubic foot models

Utilities, etc

Refrigeration

(1) 2 HP

(2) 2 HP

(2) 3 HP

(1) 7.5 HP

(2) 3 HP

(2) 7.5 HP

Heater Capacity

6

6

6

8

8

8

Humidifier

KW

2

2

2

2

2

2

 

GPH

1.0

1.0

1.0

1.0

1.0

1.0

AMPS

230V. 1Ph

230V. 1Ph

230V. 3Ph

230V. 3Ph

230V. 3Ph

230V. 3Ph

S & C

RC & RS

41

50

50

50

38

46

71

80

57

65

71

80

Fuse

50

60

60

60

60

70

100

110

70

80

100

110

Unit Weight

LBS.

2740

3540

Stay informed