Haefely Hipotronics FP-EFT 100M2 Manual 3-Phase CDN for EFT / Burst 690VAC/100A
Description
Haefely Hipotronics FP-EFT 100M2 Manual 3-Phase CDN for EFT / Burst 690VAC/100A is used for thee phase emu testing applications. The FP-EFT 100M2 can be used together with the PEFT 4010, PEFT Junior or PEFT.1 generator to inject EFT/burst impulses on the three phases supply. The unit complies to the latest edition of IEC 61000-4-4 standard. Maximum EUT voltage of 690VAC Phase – Phase, 400VAC Phase – Neutral, 110VDC, 100 A per phase EUT Current.
Features
- 5/50ns impulse shape
- 8kV impulse voltage
- manual coupling path selection
- 690Vac phase-phase
- 400Vac phase-neutral
- 100A per phase EUT Current
- Phase angle synchronization possible
Specifications
Maximum Impulse Voltage | 8kV Burst |
Maximum AC Voltage | 690V (phase – phase)
400V (phase – neutral) |
Maximum DC Voltage | 110V |
Maximum AC Current | 100A |
Maximum DC Current | 100A |
Mains Connections | 4mm safety banana sockets |
EUT connections | 4mm safety banana sockets |
Phase Sync. source | fixed between L3 and PE |
Coupling Paths | Manual Selection |
Residual pulse voltage at line input | Max. 10% of the applied impulse amplitude |
Dimensions (W x H x D) | 45 x 28 x 50 cm |
Weight | 45 kg |