QuadTech Hybrid 2000 AC/DC Hipot, IR, DCR 5 kVAC - 6 kVDC

Description

The Hybrid 2000 Wound Component Scanner is a production safety tester designed for test requirements of three-phase motors, double-wound transformers and heater related wound components. Quality verification test items for wound components consist of AC/DC Hipot (dielectric withstanding), Insulation Resistance (IR), and Impulse Winding tests. We have integrated these tests into one unit.

 

Features

  • Open/Short check (OSC) function to ensure of DUT connection
  • SUB-STEP function
  • GFI Human protection – shutdown if current imbalance >0.5mA
  • DWX Series – Impulse Winding Tester compatible
  • Flashover detection
  • Key Lock function
  • RS232 Interface (standard)
  • GPIB & Handler (optional)
  • Friendly interface
  • CE Mark
Download Data Sheet
Print
Email

Specifications

Hybrid 2000 AC/DC Hipot, IR, DCR

AC Output Voltage

Range

50V to 5000V AC

Resolution

1Volts/step

Frequency

50/60 Hz selectable

Waveform

Sinusoidal

Voltage Display

Accuracy

 ±(1% of reading + 5V)

Resolution

1 Volt

DC Current Display

Range

0.01mA to 30mA AC

Resolution

1μA

Accuracy

±(1% or reading + 5cnt) Total

High/Low Limit Test

0.001mA to 30mA AC

Low limit can be turned OFF

Insulation Resistance

Range

1MΩ – 50GΩ

Accuracy

1M – 1G: ±(3% + 10 cts), >500V

 

1G – 10G: ±(7% + 10 cts), >500V

 

10G – 50G: ± (10% + 10 cts), >500V

IR Output Voltage:

Range

50V to 5000V DC

 

Accuracy

±(1.5% of setting +5V)

High/Low Limit Test

1MΩ – 50GΩ

Low limit can be turned OFF

DC Resistance

Range

10mΩ – 100kΩ

DCR Balance

0.0001Ω – 999Ω, OFF

Stay informed