EM TEST VCS 500N8-series Combination Wave Simulator
Description
Surge pulses occur due to direct or indirect lightning strokes to an external (outdoor) circuit. This leads to currents or electromagnetic fields causing high voltage or current transients. Another source for surge pulses are switching transients originating from switching disturbances and systems faults.
Due to the characteristic of the phenomenon nearly every electrical and electronical device may suffer from such lightning events which justifies the necessity of surge tests being widely performed. Surge voltage can reach several thousands of volts and surge current is seen to reach several thousands of amps.
Although generating voltages as high as 8kV the VCS 500N8-series offer an integrated coupling/decoupling network either single phase or three-phase with a nominal current of 16A per phase. In case higher current is required its capability can be extended by an external CDN to achieve nominal currents of 100A and more per phase.
MODEL OVERVIEW
VCS 500N8 8kV Surge Generator w/o. built-in CDN; an external CDN is required
VCS 500N8.1 8kV Surge Generator with built-in 1ph CDN 250V / 16A
VCS 500N8.2 8kV Surge Generator with built-in 3ph CDN 3*440V / 16A
VCS 500N8.3 8kV Surge Generator with built-in 3-phase CDN 3*690V (L-L) / 32A
VCS 500N8.5 8kV Surge Generator with built-in 3-phase CDN 3*440V (L-L) / 32A
Features
- Surge voltage up to 8kV
- Surge current up to 4kA
- Voltage/current monitors
- Built-in CDN 1-phase or 3-phase up to 3 x 690V and 32A
- Interlock
- Warning lamp control
- Manual operation
- USB (optical link) and GPIB interface
Specifications
TECHNICAL DETAILS | |
COMBINATION WAVE 1.2/50US – 8/20US | |
Voltage (o.c.) | 250V – 8,000V ± 10% |
Front time | 1.2μs ± 30% |
Time to half value | 50μs ± 20% |
Current (s.c.) | Max. 4,000A ± 10% |
Front time | 8μs ± 20% |
Time to half value | 20μs ± 20% |
Polarity | Positive/negative/alternating |
Event counter | 1 – 30,000 or endless |
TRIGGER | |
Trigger of events | Automatic, manual, external |
CRO trigger | 5V trigger signal for oscilloscope |
Synchronization | 0° – 360°, resolution 1° |
Repetition rate | 3s – 999s, depending on the voltage |
OUTPUT | |
Direct | Via HV connectors for external coupling networks (Zi = 2ohm with optional adapter IMN 2) |
VCS 500N8.1 | Built-in single-phase coupler
AC: 250V/16A; 50/60Hz DC: 250V/10A |
VCS 500N8.2 | Built-in 3-phase coupler 3 x 440VAC / 16A; 50/60Hz
DC: 250V/10A |
VCS 500N8.3 | Built-in 3-phase coupler 3 x 440VAC / 32A; 50/60Hz
DC: 250V/20A |
VCS 500N8.5 | Built-in 3-phase coupler 3 x 690VAC / 32A; 50/60Hz
DC: 400V/20A |
Coupling mode | Line to line with 2ohm Line(s) to PE with 12ohm |
INTERFACE | |
Serial interface | USB |
Parallel serial interface | IEEE 488, addresses 1 – 30 |
SAFETY | |
Safety circuit | Control input (24Vdc) |
Warning lamp | Floating output contact |
GENERAL DATA | |
Dimensions – Weight | |
VCS 500N8 | 19″/6HU, approx. 25kg |
VCS 500N8.1 | 19″/6HU, approx. 28kg |
VCS 500N8.2 | 19″/6HU, approx. 35kg |
VCS 500N8.3 | 19″/9HU, approx. 55kg |
VCS 500N8.5 | 19″/9HU, approx. 52kg |
Supply voltage | 115/230V +10/-15% |
Fuses | 2x2AT (230V) or 2x4AT (115V) |