Fluke 435 Series II Power Quality and Energy Analyzer
Description
Think of the Fluke 435 II Power Quality and Energy Analyzer as your insurance policy. No matter what goes wrong in your facility, with the 435 II you will always be prepared. Equipped with advanced power quality functions and energy monetization capabilities, there is no electrical issue this model can't handle.
Features
- Power inverter efficiency:
- Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
- PowerWave data capture:
- Capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.).
- Energy loss calculator:
- Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
- Troubleshoot real-time:
- Analyze the trends using the cursors and zoom tools.
- Highest safety rating in the industry:
- 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
- Measure all three phases and neutral:
- With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
- Automatic Trending:
- Every measurement is always automatically recorded, without any set-up.
- System-Monitor:
- Ten power quality parameters on one screen according to EN50160 power quality standard.
- Logger function:
- Configure for any test condition with memory for up to 600 parameters at user defined intervals.
- View graphs and generate reports:
- With included analysis software.
- Battery life:
- Seven hours operating time per charge on Li-ion battery pack.
Fluke 435 II Applications
- PowerWave data capture –
- capture fast RMS values to see every waveform so you can determine how the voltage, current and frequency values are interacting
- Power inverter efficiency –
- Power inverter efficiency
- Energy monetization –
- calculate the fiscal cost of energy waste due to poor power quality
- Energy assessment –
- quantify the before and after installation improvements in energy consumption to justify energy saving devices
- Frontline troubleshooting –
- quickly diagnose problems on-screen to get your operation back online
- Predictive maintenance –
- detect and prevent power quality issues before they cause downtime
- Long-term analysis –
- uncover hard-to-find or intermittent issues
- Load studies –
- verify electrical system capacity before adding loads
Specifications
Volt |
||||
Vrms (ac+dc) |
435-II |
1 V to 1000 V phase to neutral |
0.01 V |
± 0.1% of nominal voltage**** |
Vpk |
|
1 Vpk to 1400 Vpk |
1 V |
5% of nominal voltage |
Voltage Crest Factor (CF) |
|
1.0 > 2.8 |
0.01 |
± 5 % |
Vrms½ |
435-II |
0.1 V |
± 0.2% of nominal voltage |
|
Vfund |
435-II |
0.1 V |
± 0.1% of nominal voltage |
|
Amps (accuracy excluding clamp accuracy) |
||||
Amps (ac +dc) |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 0.5% ± 5 counts |
i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 0.5% ± 5 counts |
|
1mV/A 1x |
5 A to 2000 A |
1A |
± 0.5% ± 5 counts |
|
1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 0.5% ± 5 counts |
|
Apk |
i430-Flex |
8400 Apk |
1 Arms |
± 5 % |
1mV/A |
5500 Apk |
1 Arms |
± 5 % |
|
A Crest Factor (CF) |
|
1 to 10 |
0.01 |
± 5 % |
Amps½ |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 1% ± 10 counts |
i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 1% ± 10 counts |
|
1mV/A 1x |
5 A to 2000 A |
1A |
± 1% ± 10 counts |
|
1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 1% ± 10 counts |
|
Afund |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 0.5% ± 5 counts |
i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 0.5% ± 5 counts |
|
1mV/A 1x |
5 A to 2000 A |
1A |
± 0.5% ± 5 counts |
|
1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 0.5% ± 5 counts |
|
Hz |
||||
Hz |
Fluke 435 @ 50 Hz nominal |
42.500 Hz to 57.500 Hz |
0.001 Hz |
± 0.01 Hz |
Fluke 435 @ 60 Hz nominal |
51.000 Hz to 69.000 Hz |
0.001 Hz |
± 0.01 Hz |
|
Power |
||||
Watts (VA, var) |
i430-Flex |
max 6000 MW |
0.1 W to 1 MW |
± 1% ± 10 counts |
1 mV/A |
max 2000 MW |
0.1 W to 1 MW |
± 1% ± 10 counts |
|
Power factor (Cos j/DPF) |
|
0 to 1 |
0.001 |
± 0.1% @ nominal load conditions |
Energy |
||||
kWh (kVAh, kvarh) |
i430-Flex 10x |
Depends on clamp scaling and V nominal |
± 1% ± 10 counts |
|
Energy loss |
i430-Flex 10x |
Depends on clamp scaling and V nominal |
± 1% ± 10 counts Excluding line resistance accuracy |
|
Harmonics |
||||
Harmonic order (n) |
|
DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 |
||
Inter-harmonic order (n) |
|
OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 |
||
Volts |
%f |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.1 % |
%r |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.4 % |
|
Absolute |
0.0 to 1000 V |
0.1 V |
± 5% * |
|
THD |
0.0 % to 100 % |
0.1 % |
± 2.5 % |
|
Amps |
%f |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.1% |
%r |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.4 % |
|
Absolute |
0.0 to 600 A |
0.1 A |
± 5% ± 5 counts |
|
THD |
0.0 % to 100 % |
0.1 % |
± 2.5 % |
|
Watts |
%f or %r |
0.0 % to 100 % |
0.1 % |
± n x 2% |
Absolute |
Depends on clamp scaling and V nominal |
— |
± 5% ± n x 2 % ± 10 counts |
|
THD |
0.0 % to 100 % |
0.1 % |
± 5 % |
|
Phase Angle |
-360° to +0° |
1° |
± n x 1° |
|
Flicker |
||||
Plt, Pst, Pst(1min) Pinst |
|
0.00 to 20.00 |
0.01 |
± 5 % |
Unbalance |
||||
Volts |
% |
0.0 % to 20.0 % |
0.1 % |
± 0.1 % |
Amps |
% |
0.0 % to 20.0 % |
0.1% |
± 1 % |
Mains signaling |
||||
Threshold levels |
|
Threshold, limits and signaling duration is programmable for two signaling frequencies |
— |
— |
Signaling frequency |
|
60 Hz to 3000 Hz |
0.1 Hz |
|
Relative V% |
|
0 % to 100 % |
0.10 % |
± 0.4 % |
Absolute V3s (3 second avg.) |
|
0.0 V to 1000 V |
0.1 V |
± 5 % of nominal voltage |
General specifications |
|
Case |
Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
Display |
Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated |
Memory |
8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) |
Real-time clock |
Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Environmental |
|
Operating temperature |
0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery |
Storage temperature |
-20 °C ~ +60 °C |
Humidity |
+10 °C ~ +30 °C: 95% RH non-condensing |
Maximum operating altitude |
Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V |
Electro-Magnetic-Compatibility (EMC) |
EN 61326 (2005-12) for emission and immunity |
Interfaces |