Hipotronics 815PL DC Hipot Tester 15 kV – 5 mA

Description

The 800PL Series DC Hipot testers are an economical solution to DC field testing of cables, terminations, motors, generators and other electrical apparatus. Models 815PL and 880PL-10MA offer 15kV or 80kV respectively.

All models are self-contained in a single, rugged and durable enclosure, which is complete from input line cord to high voltage output cable. Cable storage space is conveniently located inside.

The 800 Series testers feature accurate kV meter readings regardless of load current. Accurate voltage and current measurements are assured via voltage readings that are taken directly at the output of the high voltage transformer and current measurements are taken in the return leg. Safe discharging of both the test object and the high voltage transformer occur whenever the high voltage is turned off. Output power is provided by means of a full-wave voltage doubling rectifier circuit with silicon rectifiers.

 

Features

  • Rugged, portable single-piece construction
  • Shielded output cable
  • Full-wave voltage doubling rectifier circuit
  • Zero start interlock and guard circuit
  • Internal discharge solenoid
  • Meter accuracy ± 2% full scale
  • 10 mA current rating for cable charging
  • External interlock provisions
  • Three range voltmeter
  • Four range current meter
  • No internal leakage at full load
  • Instantaneous overload relay
  • Surge-limiting resistors in HV output

Hipotronics 815PL Benefits

  • Ideal for field testing – compact, lightweight and rugged makes it suitable for field orientated applications
  • Operator Safety – the power supply and test object are automatically grounded when high voltage is turned off and there is no exposed high voltage
  • Simple to Use – a minimal amount of setup time and a simple control panel allows simple testing every time
  • Accurate Leakage Current Measurement – while guard circuit eliminates stray leakage currents

Hipotronics 815PL Applications

DC Hipot testing of:

  • Cable
  • Transformers
  • Electrical Switchgear
  • Motors
  • Generators
  • Other Electrical Apparatus
Download Data Sheet
Print
Email

Specifications

General

815PL

880PL-10MA

Input Voltage

120 V, 50/60 Hz        For –A version

230 V, 50/60 Hz        For –B version

Output Voltage

0 – 15 kV

0 – 80 kV

Output Current

5 mA

10 mA

Polarity

Negative Output, positive ground

Metering

+/- 2% full scale accuracy

Ripple

0.5% per mA with rated resistance

Weight and Dimensions (W x H x D, net weight, ship weight)

815PL

16.5”W x 9”D x 18”H (42 x 23 x 46 cm)

49 lbs (22 kg)

64 lbs (29 kg)

880PL-10MA

16.5”W x 9”D x 18”H (42 x 23 x 46 cm)

78 lbs (35 kg)

90 lbs (41 kg)